BSNL
HQ BUILDING PROJECT:
General

- Covered area of typical
floor: 3000 sq. Mtr.
A.
Electrical System
- Two independent feeders
supply from electrical supply company.
- 2 No. 11 kV/ 433 volt
Transformer of 1000 KVA capacity.
- Vacuum Circuit Breaker
for 11 kV system with numerical relays for 11 kV and electronic release
for 415 volts.
- 2 nos. DG set of 1000
KVA capacity each with AMF feature for standby supply.
- Energy efficient
Luminaries with time based control of 33%, 66% and 100%.
- Special provision of occupancy
based sensors in Board room, conference hall , CMD, and Directors areas.
- 480 KVA UPS backup for
emergency lighting at critical locations and computers and monitoring
services
- Provisions of electrical
risers by sandwiched insulated compact bus risers.
- Automatic Power factor
improvement capacitor panel.
- Automatic water supply
system in various tanks and hydro-pneumatic system for toilets.
B.
Building Management System
- Electronic Access
control cards attendance system on each floor.
- CCTV monitoring and
recording inside & outside the building with digital DVR’s.
- Monitoring and control
of Electrical Equipments like Air-conditioning system, substation, D.G.
sets, Elevators sets, fire fighting system pumps etc.
- 4 nos., 12 passenger
capacity Elevators upto 9th floor and 2 Nos.12 passengers upto 6th
floor and 2000kg capacity freight Elevators form basement to 9th
floor..
- Monitoring of
addressable Fire Detection system for building and various equipment
rooms.
- Monitoring of condition
based periodical maintenance of equipments installed
- Emergency Public address
system with talk back.
C.
Air-Conditioning System
- Energy efficiency,
automatic capacity controlled, 3 nos 100 TR Air Cooled roof top chillers
and 2 Nos VAM with CNG/ Diesel fired Air conditioning system suitable for
both cooling and heating purpose.
- Floor wise AHU system.
- Provision of independent
FCU’s for critical areas.
- Provision of Fire
Dampers to regulate Air Conditioning in case of fire.
- Air Conditioning System
controlled through Building Management System for energy efficiency.
- Ventilation system for
both the basements. Stair case and Lift shafts by Inlet and Exhaust Propellers/Fans.
D.
Fire Detection and Protection System
- Fire Detection and
Suppression system as per National Building Code and Delhi Fire Services
norms.
- Wet riser System and
hydrants for internal and external building purpose.
- Analogue addressable
Fire Detectors of different types suiting to the locations integrated with
the Building Management System and Public Address System.
- Water sprinkler System
in the building and Common Services Areas.
- Automatic high Velocity
water spray system for 33kV Outdoor Transformers.
- Pressurization of Lift
Lobby, Lift well and Staircases to prevent Spreading of Fire.
- Underground and Overhead
storage tank for Fire Protection System with Automatic Pumping sets Jockey
pump, standby Diesel driven Pumps, all integrated with the Building
Management system.
-
.